A 4-pole, three-phase induction motor runs at 1750 rpm on a 60 Hz supply. What is its slip?
| Given |
|
|---|---|
| Find | Slip (%) |
Solution
ns = 120f/p = 120 × 60/4 = 1800 rpm
s = (ns − n)/ns = (1800 − 1750)/1800 = 2.78 %
FE Electrical and Computer · area 10 · 8–12 items
Power Systems carries 8–12 items, the largest area after Circuit Analysis and Mathematics, tied with Digital Systems. It starts where AC circuit power leaves off and adds three-phase connections, lines, transformers and rotating machines.
Updated Oct 29, 2026 · Not affiliated with NCEES.
Four subtopics in the July 2020 specification:
A 4-pole, three-phase induction motor runs at 1750 rpm on a 60 Hz supply. What is its slip?
| Given |
|
|---|---|
| Find | Slip (%) |
Solution
ns = 120f/p = 120 × 60/4 = 1800 rpm
s = (ns − n)/ns = (1800 − 1750)/1800 = 2.78 %
A transformer has 500 turns on the primary and 50 turns on the secondary. A 4 Ω load is connected to the secondary. What impedance is seen at the primary?
| Given |
|
|---|---|
| Find | Impedance referred to the primary (Ω) |
Solution
Zp = (Np/Ns)2 · Zs
Zp = (500/50)2 × 4 Ω = 400 Ω
The no-load voltage at the receiving end of a transmission line is 13.2 kV. Under full load, the voltage drops to 12.6 kV. What is the voltage regulation?
| Given |
|
|---|---|
| Find | Voltage regulation (%) |
Solution
VR = (Vnl − Vfl)/Vfl × 100 %
VR = (13.2 − 12.6)/12.6 × 100 % = 4.76 %
A balanced three-phase delta-connected load draws 24 kW at 480 V line-to-line with a power factor of 0.8. What is the phase current in each delta branch?
| Given |
|
|---|---|
| Find | Phase current in each delta branch (A) |
Solution
Pph = 24 kW/3 = 8 kW, Vph = VLL = 480 V (delta)
Iph = Pph/(Vph · pf) = 8000/(480 × 0.8) = 20.8 A
A dc shunt motor with armature resistance 0.5 Ω draws 40 A from a 240 V supply. The field current is 2 A. What is the back EMF?
| Given |
|
|---|---|
| Find | Back EMF Eb (V) |
Solution
Ia = IL − If = 40 − 2 = 38 A
Eb = V − IaRa = 240 − 38 × 0.5 = 221 V
A three-phase, 6-pole induction motor operates at 1164 rpm on a 60 Hz supply. What is the frequency of the rotor currents?
| Given |
|
|---|---|
| Find | Rotor current frequency fr (Hz) |
Solution
ns = 120f/p = 1200 rpm, s = (1200 − 1164)/1200 = 0.03
fr = s · f = 0.03 × 60 Hz = 1.8 Hz
A balanced wye-connected three-phase generator has a phase voltage of 7.2 kV. If it delivers 15 MW at 0.85 power factor lagging, what is the line current?
| Given |
|
|---|---|
| Find | Line current IL (A) |
Solution
P = 3VphIph·pf, IL = Iph (wye)
IL = 15 × 106/(3 × 7200 × 0.85) = 817 A
A three-phase transformer bank consists of three single-phase transformers, each rated 7200:240 V. The primaries are connected in delta and the secondaries are connected in wye. What is the line-to-line voltage on the secondary side?
| Given |
|
|---|---|
| Find | Secondary line-to-line voltage (V) |
Solution
Vph,sec = 240 V (winding voltage)
VLL,sec = √3 × 240 V = 415.7 V
Two 230 kV buses are joined by a lossless line with a series reactance of 120.0 Ω per phase, and both voltages are held at 230 kV line-to-line. What are the maximum three-phase real power the line can carry and the power at a 30° power angle?
| Given |
|
|---|---|
| Find | Three-phase Pmax and P at δ = 30° (MW) |
Solution
P = (VSVR/X) sin δ (VLL values give the three-phase total)
Pmax = (230 kV)2/120 Ω = 441 MW, P30 = 441 × sin 30° = 220 MW
A three-phase transformer rated 5 MVA, 13.8 kV/480 V, has a 5.0 % impedance. Assuming an infinite source and a bolted three-phase fault at the 480 V terminals, what is the secondary short-circuit current?
| Given |
|
|---|---|
| Find | Secondary short-circuit current (kA) |
Solution
Irated = S/(√3 · VLL) = 5 × 106 VA/(√3 × 480 V) = 6014 A
Isc = Irated/Zpu = 6014 A/0.05 = 120.3 kA
A single-phase load draws 7.50 kW at 0.70 power factor lagging from a 240 V, 60 Hz supply. What capacitance connected in parallel raises the power factor to 0.95 lagging?
| Given |
|
|---|---|
| Find | Parallel capacitance C (µF) |
Solution
QC = P(tan θ1 − tan θ2) = 7500 × (1.0202 − 0.3287) = 5186 var
C = QC/(ωV2) = 5186/(2π × 60 × 2402) = 238.8 µF
A single-phase AC motor delivers 20 hp from a 240 V rms supply with 80 % efficiency and a lagging power factor of 0.85. Taking 1 hp = 745.7 W, what rms current does it draw?
| Given |
|
|---|---|
| Find | Supply current I (A) |
Solution
Pin = Pout/η = (20 × 745.7 W)/0.80 = 18,643 W
I = Pin/(V · pf) = 18,643/(240 × 0.85) = 91.4 A
An industrial facility is billed based on peak monthly kVA demand and total kWh consumption. The plant currently operates at a peak load of 500 kW with a power factor of 0.75. The facility manager proposes installing capacitor banks to improve the power factor to 0.95. Assuming the real power demand (kW) and hours of operation remain identical, which of the following describes the most likely impact on the utility bill?
Solution
S1 = 500/0.75 = 667 kVA → S2 = 500/0.95 = 526 kVA
kW × hours unchanged → kWh charge unchanged.
A single-phase transformer rated at 25 kVA has an efficiency of 96% at full load with unity power factor. What are the total losses at full load?
| Given |
|
|---|---|
| Find | Total full-load losses (kW) |
Solution
Pout = S · pf = 25 kW, Pin = Pout/η = 26.04 kW
Ploss = Pin − Pout = 1.04 kW
A balanced three-phase motor on a 480 V line-to-line source draws 25 A line current at a power factor of 0.85. Its overall efficiency is 90 %, and it runs at 1750 rpm. What is the shaft output torque?
| Given |
|
|---|---|
| Find | Output torque T (N·m) |
Solution
Pout = η√3VLLIL·pf = 0.90 × √3 × 480 × 25 × 0.85 = 15.90 kW
ω = 2πN/60 = 2π × 1750/60 = 183.3 rad/s
T = Pout/ω = 15,900 W/183.3 rad/s = 86.8 N·m
A single-phase transformer has a turns ratio of 10:1 (primary to secondary). If the primary voltage is 2400 V, what is the secondary voltage under no-load conditions?
| Given |
|
|---|---|
| Find | Secondary voltage Vs (V) |
Solution
Vs = Vp(Ns/Np) = 2400 V/10 = 240 V
Answer every question to see your score
For a balanced load, total power uses line quantities:
P = √3·VL·IL·cos θ S = √3·VL·IL
Balanced problems are easiest on a per-phase basis: convert to an equivalent wye, solve one phase, multiply power by three. Machines add a few more relations, starting with synchronous speed ns = 120f/p in rpm and slip s = (ns − n)/ns; the Handbook keeps them in the AC Machines section of its Electrical and Computer Engineering chapter (NCEES errata notice).
Common traps in power systems
Sources: Chapman, Electric Machinery Fundamentals; Glover, Overbye and Sarma, Power System Analysis and Design.
Single-phase complex power is set up in Circuit Analysis; rectifiers, inverters and drives are Electronics. In this hub, three-phase and transformer questions are owned here. Electrical safety and grounding are part of Ethics and Professional Practice, on the FE practice test.
8–12 of 110, roughly a tenth of a form.